Innovating power.
Troubleshooting & Fault Clearance
–
Page 119
Solar inverter | V1.7
Error code 55
Output voltage is
asymmetrical.
Error code 56
Battery bank is not
connected or the
fuse has been
activated.
Check the battery
bank, the fuses and
the connection. If
unsuccessful, the
device must be
repaired.
Situation
Resolution
Error
code
Description
60
Power feedback in the
inverters is disrupted.
*
Restart the inverter
*
Check all connections
*
Are the current sharing connections
properly wired?
71
The firmware version of
the inverter are not
identical
*
Check the firmware versions on each
inverter
*
Update all inverters to the same
firmware
72
The output current of the
inverter is different
*
Restart the inverter
*
Check the connections
80
Error in communication
bus CAN
*
Check the communication connections
*
Check on the installation of the parallel
card
*
Restart the inverter
81
Connection error
82
Loss of synchronization
83
Battery voltage is
different
* Check the battery voltage of all the inverters
84
AC input voltage and
frequency are recognized
as different.
*
Check the mains connections at input
*
Restart the inverter
85
AC output currents
are different
*
Check the mains connections at the output
*
Restart the inverter
86
The setting of the AC
output mode is
different
* Switch off the inverter and check the settings
in Menu 28