AX M2 Series 3-5 kW | Solar inverter
Troubleshooting & Fault Clearance
–
Page 118
Solar inverter | V1.7
The buzzer
beeps
continuously
and the red
PED is
blinking.
Error code 07
The inverter has
detected an
overload (> 110%)
Reduce the load by
switching off
individual loads or
try the bypass
mode.
Error code 05
Output short circuited.
Check the load
network and
remove defective
loads. Check the air
circulation,
ventilators and
room temperature
(too high).
Error code 02
Overtemperature
on inverter (> 100
°C).
Check the air
circulation,
ventilators and
room temperature
(too high).
Error code 03
The battery bank is
overloaded.
Switch the system
off and check the
inverter and the
battery bank.
The battery bank
voltage is too high.
Error code 01
Ventilation error
Device must be
repaired: ventilator
replacement.
Error code 06/58
Output is
abnormal (inverter
voltage < 190 or >
260 VAC)
Attempt: Reduce the
load. If this does
not bring a change,
the device must be
repaired.
Error code
09.08.53/57
Internal error.
Device must be
repaired.
Error code 50
PFC overcurrent or
overvoltage.
Restart the device.
If the error occurs
again, contact a
specialized service.
Error code 51
Overcurrent or current
spike.
Error code 52
DC intermediate
circuit
error.