Connection
–
Page 69
Solar inverter | V1.7
9.5.1
Wiring instructions
CAUTION
Ensure that the lengths of all battery cables are equal. Otherwise, there is a voltage
difference between the inverter and battery which will cause the parallel inverter to not
function.
CAUTION
Install a fuse on the battery and AC input side. This ensures that the inverter can be
safely disconnected during maintenance work.
Recommended battery cable terminal size for each inverter:
Model
Cable
size
Ring cable lug
Tighten-
ing torque
Cable
mm2
Measurements
D
(mm)
L
(mm)
3KW
1*70mm²
70
6.4
49.7
2~ 3 Nm
2*25mm²
25
6.4
49.7
5KW
1*70mm²
70
6.4
49.7
2~ 3 Nm
2*25mm²
25
6.4
49.7
Recommended AC input and output cable size for each inverter:
Model
AWG
Tightening torque
3KW
6mm²
1.2~1.6Nm
5KW
10mm²
1.4~1.6Nm
Recommended power switch specification of the battery for each inverter:
Model
3KW
150A/60VDC
5KW
125A/80VDC
If you would like to use only one fuse on the battery side for the entire system, the
nominal value of the fuse should be the n-fold of the current of 1 device. "X" stands for
the number of inverters switched on in parallel mode.