AX M2 Series 3-5 kW | Solar inverter
Solar inverter | V1.7
Control and display elements - Page 40
23
Bypass mode in
case of overload:
In the case of
overload in inverter
mode, the device
switches to bypass
Bypass function (not
permissible)
When selected, the inverter
does not function in the
bypass/ECO mode.
Bypass function off
When selected and the ON
button has been pressed,
the inverter can only
operate in the bypass/ECO
mode if mains power is
available.
Bypass function on
When this option is
selected and, independent
of whether the ON button
has been pressed or not,
the inverter operates in the
bypass mode if mains
power is available.
25
Storing the errors:
(FAULT CODES)
Display error code
–
on
Display error code
–
off
26
Defining battery
bank, bulk
charging voltage:
3KW Pre-setting: 28.2V
5KW Pre-setting: 56.4V
When menue point 05 "USE" is selecte
bulk charging voltage can be set here.
The setting range extends from 24.0 V to 32.0 V for
the 3-kW model and from 48.0 V to 64.0 V for the 5-
kW model. The increase per each click is 0.1 V.