Control and display elements - Page 43
Solar inverter | V1.7
Charging conduct or
duration of the bulk
charge.
When "user defined" is selected in program 05,
this program can be set.
The setting range extends from 5 min to 900
min. The increment of each click is 5 minutes.
Otherwise, maintain the automatic charging
time.
33
Charge balance of the
battery bank
(equalizing)
(only available when
"USE" is selected
under 05).
Activate battery equalizatio
n
Deactivate
battery
equalizzation (pre-set)
34
Battery bank
voltage during
charge
equalization.
3KW Pre-setting: 29.2V
5KW Pre-setting: 58.4V
The setting range extends from 24.0 V to 32.0 V
for the 3-kW- model and from 48.0 V to 64.0 V for
the 5-kW model. The increment of each click is
0.1 V.
35
Charge
equalization
duration for the
battery bank.
60min (pre-set)
The setting range
extends from 5 min to
900 min. The increment
of each click is 5
minutes.
36
Charge
equalization
TIMEOUT of the
battery bank.
120min (pre-set)
The setting range
extends from 5 min to
900 min. The increment
of each click is 5 min.