14 TEMPERATURE PROTECTION
The difference between Supply temperature and Inlet Temperature is continuously monitored. A too big difference
can indicate a defective pump or a clogged heat exchanger. To protect the water heater, the burner controller
reduces the input when the temperature difference ΔT becomes too high:
At maximum water heater input
ΔT
is limited to 18 °C (32 °F)
In between 18 °C (32 °F) and 26 °C (47 °F) water heater input modulates between minimum and maximum.
At minimum water heater
input ΔT
above 26 °C (47 °F)
Above ΔT = 31 °C (56 °F), the water heater is switched OFF during
HX
_
Diff_Max_Wait_Time
.
Relevant factory set variables
Parameter
Level
Factory Setting.
HX Diff DeltaT Min
3: Factory
18 ºC (32 ºF)
HX Diff Max Wait Time
Wait time after upper limit primary heat exchanger dif-
ferential has been exceeded.
3: Factory
0 Sec.
15 ERROR INFORMATION.
Errors can be divided in three groups:
• Non-volatile locking errors (can only be reset by the reset button).
• Blocking errors (will disappear when error is gone)
• Warnings (will disappear when the warning is gone, not stored in the BCU)
The water heater pump will continue to run during most locking and blocking error codes
. This is to prevent the
freezing of the Heating circuit when the water heater is in error during the winter period. For some non-volatile
lockouts the pump will not be running, also see the error tables in this chapter for more details.
Water heater history.
The last 15 lockouts and 15 blocking errors are stored in the water heater control. This water heater history can be
shown via the Water heater History screen via the installer water heater status menu in one of the advanced dis-
plays.
•
Successful ignitions
•
Failed Ignitions
•
Flame Failures
•
Anti-legionella count
•
Total system run time
•
CH Burner Hours
•
DHW Burner Hours
0
20
40
60
80
100
120
10
15
20
25
30
35
40
B
oi
ler
inp
ut
[%]
Delta T [
°C]
Boiler input control
High power
Low power
Boiler Off
31
26
18
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......