3. Set parameter 92 and 93
The fan speed has to be changed in the software of the water heater according to the tables below:.
Water heater type
fan speed
high fire
parameter 92
Fan speed low fire
parameter 93
Internal
igniter
CB 85
6500
1850
CB 105
7300
2000
CB 125
7200
1950
CB 155
6000
2000
1. From status screen, press MENU button once.
2.
Press UP/DOWN ↑ ↓ to select "Settings" and press ENTER
3.
Press UP/DOWN ↑ ↓ to select "Water heater Settings" and press ENTER
4.
Enter installer password by pressing UP/DOWN ↑ ↓ and LEFT ← / RIGHT →.
5.
Press UP/DOWN ↑ ↓ to select "Water heater parameters" and press ENTER
6.
Press UP/DOWN ↑ ↓ to select parameter “(92) Fan Speed Maximum” and press ENTER
7.
Press UP/DOWN ↑ ↓ to adapt the fan speed according to the table and press ENTER
8.
Press UP/DOWN ↑ ↓ to select parameter “(93) Fan Speed Minimum” and press ENTER
9.
Press UP/DOWN ↑ ↓ to adapt the fan speed according to the table and press ENTER
To return to the status screen, press ESCAPE
or MENU
4 times, or RESET
once.
Check during start-up of the water heater no gas mixture is leaking
on all parts that have been apart!
4. Adjust the O
2
/ CO
2
percentage
CO
2
/ O
2
(%)Propane G31
water heater type
max load
min load
CB 85
4.9 / 10.5
6.7 / 9.3
CB 105
5.2 / 10.3
6.7 / 9.3
CB 125
5.2 / 10.3
6.4 / 9.5
CB 155
5.2 / 10.3
6.4 / 9.5
REMARKS:
Allowed tolerances are O
2
± 0.2 and CO
2
± 0.1
All values measured without front door.
5. Confirmation
When finished:
- Apply the corresponding sticker at the appropriate position in the water
heater.
-
Mark the box “Propane” for the used gas type.
-
Mark the box “Type”, indicating that the correct parameter values have
been set for this boiler type.
It is possible to improve the ignition spark by using an external ignition transformer.
Available on request, see the accessories list.
Please ensure the water heater is clearly labelled if operating on propane supply!
NOTICE
WARNING!
E73.0010.999
WARNING!
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......