E93.1803.901 HW
85
13.1.15
O
N BOARD
HMI
AND
LED
COLORS
On the burner controller a basic on-board Human Interface (HMI) is available which consists of a push button and
a 2 color (red/green) LED. These are used to indicate basic status information about the control.
Control operational
When the control is operational and there are no errors present the LED will show as a constant green color.
Control locked
When the control is locked the LED will show as a constant red color. When the control is locked the control can
be reset by using the push button. When the reset has been accepted the control is reset and the status LED will
return to show the green color
Control blocked
When the control is blocked the LED will alternate between green and red with a 1 second interval. When the
blocking error is solved the LED will return to show only the green color.
Exceptions
In case the communication between the main and watchdog processor cannot be established the LED will not
follow the status from the control. In this situation the watchdog processor will reset in an attempt to restore the
communication. When this occurs the LED will appear as green with short pulses in which the LED is off.
13.1.16
F
LAME DETECTION
When the water heater is firing, and the flame is not detected anymore, the gas valve will be closed, and the control
will perform a post-purge, after which a restart will take place.
The presence of a flame is measured through the flame rod that points into the flame. The flame current is measured
by the control as ionization in micro amps (
μA).
When the flame current is above Flamerod_Se Flamerod_Hysterese (1.0
μA + 0.5 μA) a flame will be pre-
sent. When the flame current is below Flamerod_Setpoint (1.0
μA) the flame will not be present.
13.1.17
F
LAME RECOVERY
When the ionization current is too low, the system responds by increasing the minimal fan speed, in order to keep
the flame present. This is done by increasing the minimal fan speed when the ionization current is too low.
Whenever the ionization current is high enough, the minimal fan speed will be decreased again. When the flame
still disappears the minimal fan speed will be increased for the next burn cycle.
• When the flame current is below Flamerod_Se Flamerod_Delta (1.0 μA + 0.2 μA) the minimal fan speed
will be increased.
• When the flame current is above Flamerod_Se Flamerod Flamerod_Delta * 2 (1.0 μA + 0.2 μA +
0.4
μA) the minimal fan speed will be decreased.
When the flame still disappears the minimal fan speed will be increased for the next burn cycle.
When the system successfully completes a burn cycle, the minimal fan speed will be reset to the set minimal fan
speed in the system.
No. of flame losses
Description
0
Minimal fan speed as set in the system
1
In between minimal and ignition fan speed
2
Ignition fan speed
Status LED
Reset button
900MN
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......