E93.1803.901 HW
78
13.1.3
P
ROTECTED MENU ITEMS
The display supports 3 different access levels; each with its own set of available menu items/parameters:
Level
Description
0: User
Basic info and settings only that are accessible for everyone.
1: Installer
Advanced information and settings; only to be accessed by an experienced installer/person.
2: Factory
Highest level information and settings, only available/relevant for factory Engineers.
Access the Installer and Factory user level by entering the correct access code (password) for the desired user
level. If a certain menu item has been selected, the following password screen will appear where a specific pass-
word has to be entered:
Users are only allowed to change parameters not needing a password. Installers have to contact their supplier for the password because of
safety.
Changing protected/safety parameters should only be conducted by experienced, licensed wa-
ter heater operators and mechanics. Hazardous burner conditions can happen with improper
operations.
Enter the password with the following steps:
1. Use the UP/DOWN
↑↓ button to adjust the first number
2. Press CONFIRM or RIGHT
→ to confirm and to go to the following number
Repeat this action for all numbers to enter the password.
During this action, if you want to return to the previous screen, just press MENU or ESC to cancel. After
the password is entered in correctly press ENTER/RIGHT to confirm and access the menu item.
When a correct password is entered the selected user-level is unlocked. This is displayed by an icon (padlock or
key) in the top bar, the associated number indicates which user-level is unlocked (1:Installer, 2:Factory).
The following menu items also require a password*:
(Sub) Menu item
Location inside menu
Startup Settings
Settings / General Settings / Other Settings / Startup Settings
Boiler Parameters
Settings / Boiler Settings / Boiler Parameters
Module Cascade Settings
Settings / Boiler Settings / Module Cascade Settings
Boiler Cascade Settings
Settings / Boiler Settings / Boiler Cascade Settings
13.1.4
D
E
-
AERATION
S
EQUENCE
The “De-Aeration” sequence is a safety function that starts at every power ON of the water heater and is used to
remove the air from the heat-exchanger. The DAir sequence does not start after a general reset (like the locking
error reset or 24 hours reset)
The display will show the following string during DAir sequence:
• “Dair Running”
• “Dair Error Water Pressure”
The De-Air sequence can be cancelled by the user by pressing the OK button for min. 5 seconds.
13.1.5
L
ANGUAGE SETTINGS
The display supports the following languages:
▪
Chinese
▪
German
▪
Romanian
▪
Croatian
▪
Greek
▪
Russian
▪
Czech
▪
Hungarian
▪
Slovak
▪
Dutch
▪
Italian
▪
Slovene
▪
English
▪
Polish
▪
Spanish
▪
French
▪
Portuguese
▪
Turkish
The following paragraph describes how to change the display language. No matter which language you have set,
the menu icons will always remain universal
WARNING
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......