E93.1803.901 HW
109
17 SYSTEM TEST.
For testing the system at fixed power rates, a system test can be activated via the Installer menu. Via the system
test the water heater can be started without CH or DHW being present. The system test has priority.
The following modes are available:
System test mode
Description
0
Not active
System test mode not active
1
Fan only
The fan is forced to run at maximum speed without starting the water heater
2
Low power
The water heater starts and after the ignition period has finished the water heater stays at low
power
3
Ignition power
The water heater starts and stays at ignition power
4
High power
The water heater starts and after the ignition period has finished the water heater stays at high
power
5
High power limited
The water heater starts and after the ignition period has finished the water heater stays at high
power limited by the parameter
CH_ max_ power
6
High limit error test
Simulates the
Max_Temp_Error
7
Low water cut off 1 error test
Simulates the
LWCO_1_ Error
8
Low water cut off 2 error test
Simulates the
LWCO_2_ Error
Before running the system test modes first check if the heat can be dissipated. Note that
during this mode the supply temperature can be raised above 95 ºC (203 ºF). When this
temperature is reached the water heater will switch OFF. When the supply temperature
cools down to 90 ºC (194 ºF) the water heater will start again.
During the system test the water heater and system pump will be ON.
As the water heater will run at fixed power rates there is no setpoint control active.
Also the flame recovery is not active during system test demand. All other safety functions
remain active.
The system test automatically stops after 10 minutes, after which the system continues with normal demand han-
dling. When the system test mode is changed during an active system test, the 10-minute timer is restarted.
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......