E93.1803.901 HW
57
Typical examples
A
:
Twin pipe system with separate pipes for flue gas and air supply
C63
B
:
Twin pipe system with separate pipes and concentric roof terminal
C33
C
:
Single pipe for flue gas outlet only (air supply from water heater room)
B23
D
:
Concentric pipe for flue gas/air supply (roof-mounted)
C33
E
:
Concentric pipe for flue gas/air supply (wall-mounted)
C13
F:
Separate air supply duct & flue duct in different pressure zone
C53
NOTICE: specific resistance values of ECO-HS flue gas and air intake parts are used for these
examples. Other suppliers can have deviating values!
10.1.6
E
XAMPLE
A:
T
WIN PIPE SYSTEM WITH SEPARATE PIPES FOR FLUE OUTLET AND AIR SUPPLY
Calculation example with given lengths: checking resistance
Water heater type:
CB 155
Flue gas
Diameter: 150 mm
quantity
Pa
Pa total
Straight tube /m
total
9
1.3
11.7
Bend
90°
2
4.9
9.8
Flue outlet
zeta=1.0
1
6.3
6.3
Total resistance flue gas outlet:
27.8
A
ir
su
pp
ly
Diameter: 150 mm
quantity
Pa
Pa total
Straight tube /m
total
8
1.5
12.0
Bend
90°
2
5.7
11.4
Air inlet
zeta=1.0
1
7.3
7.3
Total resistance air supply:
30.7
Total resistance flue gas outlet and air supply:
58.5
The total resistance is less than 200 Pa.
This flue gas/ air supply system is functional.
NOTE: ECO specific resistance values are used in this example.
Flue and air pipes of other suppliers can have other values
CB 155
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......