E93.1803.901 HW
145
Error logging
Errors will be logged for a stand-alone system or for a complete cascade system (based on the cascade settings).
The display will monitor the error number(s) it receives from the water heater(s): new errors will be stored in the
error log.
An error will be logged with a (Real Time Clock) time stamp (date and time) when the error was detected and a
water heater ID of the water heater on which the error was detected.
Note: the error log is a completely different error logging mechanism than the one used by the burner control itself.
Therefore, the error log is different from the (internal) error history of the burner control.
The error log can be seen from the error log menu, which is located in the Information menu. In the Error log menu
the following options can be selected:
(Sub) Menu item
Description
Error Log
Show the error log (based on the selected filter options)
Filter Error Type
Filter errors based on the Error type (lockout/blocking)
Filter Boiler ID (Cascade System only)
Filter errors based on Boiler ID (Managing, Dep 1, Dep2, etc.)
Clear Error Log
Clear the error log (protected by password)
When no filtering option is selected (disabled) the error log will show all errors for that category. So, if both filters
are disabled, the error log will show all the errors in the log.
The following table describes what is displayed inside the Error log:
Service reminder
The Service reminder will remind the owner/user of the appliance to service the appliance every 2000 burn hours.
When service is not done within this time, a message will be shown on the screen: "Service is required!", alter-
nating with the normal status display.
NOTE: with the message "Service is required" the boiler keeps running , but maintenance must be done before
resetting this message.
When the Service reminder has become active, the time it takes before service is actually done is being logged (in
hours). This time is called the Service Overdue Time.
The Service reminder can be reset by the installer who services the appliance.
Service status information can be viewed at: Menu/ Information/ Service:
(Sub) Menu item
Description
Service history
View the Service history (log). For each service moment the Service overdue counter is stored. When the over-
due counter is 0 hrs., it means service was done before the Service reminder was active. The log is ordered so
the most recent service moment is shown first (on top of the list).
Burn hours since last service
Shows the number of burn hours since the last service moment.
Burn hours till service
Shows the number of burn hours until service is required.
Reset service reminder
Reset the Service reminder (and store Service overdue counter in the service history).
Installer must enter the installer password first before it can be reset.
End of customer section.
Error Log con-
tent
Description
First line
-
Boiler ID (for which boiler the error was detected
–
cascade system only)
-
Error code (internal)
-
Error number
-
Error type (lockout/blocking)
Second line
- Error description
Bottom line
-
Time Stamp (date and time) when the error was detected (in the format configured in the
Date & Time settings menu)
-
The selected error index from the total numbers of errors in the (filtered) error log
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......