21 MAINTENANCE CHECKLIST
Allowing the water heater to operate with a dirty combustion chamber will hurt operation. Fail-
ure to clean the heat exchanger as required by the manual and dictated by the operating
location
could result in water heater failure, property damage or personal injury.
Such product failures ARE NOT covered under warranty
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the
equipment is operating safely and efficiently. The owner should make necessary arrangements with a qualified
heating contractor for periodic maintenance of the heater. The technician must also inform the owner that the lack
of proper care and maintenance of the water heater may result in a hazardous condition.
Maintenance Table
Inspection Activities
Date Last Completed
1
st
Year 2
nd
Year 3
rd
Year 4
th
Year
Near wa-
ter heater
piping
Check system and water heater piping for any sign of
leakage. Take off water heater cover and inspect con-
nections in water heater for any leaks or corrosion
Vent
Check condition of all vent pipes and joints
Check to ensure vent termination not blocked or ob-
structed
Gas
Check gas piping, test for leaks and signs of aging.
Record gas pressure and note pressure drop upon
start-up. Record O
2
/ CO
2
at high and low fire
Visual and
Temperature
Do visual inspection of all system components and
verify programmed temperature settings
Connections Check wire connections and make sure they are tight
Combus-
tion cham-
ber
Check burner tube and combustion chamber coils.
Clean with nylon brush and vacuum. Avoid touching
white ceramic fiber. Also see maintenance section of
manual
Spark igniter Ensure spacing of igniter prongs are aligned properly.
Replace
NRV
Replace non-return valve every year. And be sure it is
not leaking gas after reassembling.
Conden-
sate trap
Disconnect condensate hose and trap. Ensure no
blockage, rinse and clean out. Fill completely again
with fresh water and re-install
Relief Valve Check to make sure it is not weeping
Pump
and Fan
Listen to sound of the pump and fan. If either makes
noise during operation, it is recommended to replace
the part.
Low water
cut-off
Check the LWCO is not leaking and check for right
pressure value by draining the water from the water
heater and comparing the value with a calibrated me-
ter equipment
Homeowner
Question homeowner before maintenance if they have
any issues and after done, confirm activities you per-
formed during maintenance visit
Chemical
additions
Check the chemical additives and add or renew if the
mixing ratio is out of spec.
Mixing Ratio
WARNING
Содержание CB 105 HW
Страница 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Страница 70: ...E93 1803 901 HW 71...
Страница 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Страница 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Страница 128: ...E93 1803 901 HW 129...
Страница 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Страница 130: ...E93 1803 901 HW 131...
Страница 145: ......
Страница 146: ......