Function of VS 300
43
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
4.4.1
High pressure monitoring
High pressure is detected in the high-pressure line by a continuous transducer with current output. When high
pressure rises to a definable limit
t
c max
(Parameter S265), the first stage is unloaded immediately on exceeding
the
t
c limit
regardless of the number of compressors running. Additional stages are unloaded after the basic un
load time has elapsed. This continues until pressure drops to a level below the set limit or a definable number of
compressors remain running.
The number of compressors remaining running after exceeding
t
c max
can be defined (Parameter S277). The
default value is a function of the number of compressor stages and must always be redefined following first start
or after chaning the number of compressors. The following table shows the default as a function of number of
compressor stages:
No. of compressor stages
Default: No. of compressor
stages in HP fault
1 - 2
1
3 - 5
2
6 - 7
3
8 - 10
4
11 - 12
5
When all compressors are working, unloading of the first compressor takes place without delay. An exception is
heat recovery (HR) mode.
Compressor unload does not take place in HR operating mode. No additional compressor is loaded when the
pressure limit is attained, regardless of any demand for additional load.
Control algorithm
HP monitoring
Limit HPS cutout
Limit HP cutout
Limit comp. dis
able
Limit comp. en
able
Tim
e
Compressor
enable
not dis
abled
Comp. disable
high
pressure
t
c
ZNR. 51203 62
630 E0
High HP alarm is generated after a definable delay if the limit set for Disable Comp. (Parameter S225 / S265) is
exceeded. Alarm priority can be defined. No alarm is generated in heat recovery mode. No additional capacity
stages are loaded when a HP alarm is active.
The
High HP
alarm and compressor disabling are not reset until pressure drops below the level set for
Enable
Comp.
(Parameter S226 / S266).
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...