Parameter List and Menu Structure of VS 300
112
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
8.1.15 Parameter List C: Service / Check Mode - Defaults Relay Outputs
Parameter
No.
Function
Description
Range
Default
Dim.
Displayed / Condition
C010
nr 01
..
nr [m]
CL1
Default actuating sta
tus of relay/control
stages
0: Output not
actuated
1: Output
actuated
0
-
Minimum of one stage must be defined in CL1:
S301 > 0
[m] =
Basic configuration (<=4):
[
Value S301
]
1st expansion stage (<=8):
[
Value S301
]
2nd expansion stage (<=12): [
Value S301
]
C020
nr [n]
..
nr [o]
CL2
Default actuating sta
tus of relay/control
stages
0
-
Minimum of one stage must be defined in CL2:
S331 > 0
[n] = [
Value
S301
] + 1
[o] = Basic configuration (<=4):
[n][
Value S331
]
1st expansion stage (<=8):
[n][
Value S331
]
2nd expansion stage (<=12): [n][
Value S331
]
C030
nr [p]
..
nr [q]
Default actuating sta
tus of internal alarm
relay / alarm control
stages
0
-
Only visible when at least 1 stage is parameterised as
an alarm relay: S376 >0:
S376 = 1
[p] =
not applicable
[q] =
Basic configuration:
4
1st expansion stage:
8
2nd expansion stage:
12
S376 = 2
[p] =
Basic configuration:
3
1st expansion stage:
7
2nd expansion stage:
11
[q] =
Basic configuration:
4
1st expansion stage:
8
2nd expansion stage:
12
C040
nr 01
..
nr 02
Alarm card
Default actuating sta
tus of alarm relays
0
-
Always shown
(Outputs can however
only
be actuated when
VS 300 is fitted with optional alarm relay module.)
Number of relay stages CL1
[ValueS301]
+ Number of relays CL2
[Values S331]
+ number internal
alarm relay
<= Number of relays stages VS 300 (varying with expansion stage/number of relay
stages can be 4/8/12)
Parameter List C:
To change values set access level to
setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...