Startup of VS 300
61
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
5
Startup of VS 300
The operator terminal AL 300, the store computer CI 3000 or the PC-Software LDSWin are used to set parame
ters on the controller at startup and for subsequent changes.
The controller should only be used with compatible versions of the PC software LDSWin, otherwise
the range of functions could be restricted.
Tip
: The latest version of LDSWin should be used at all times.
Before commissioning the VS 300 Pack Controller, preparations must be made for installing it in the control
panel. Basic settings must also be made on the hardware and in the software.
5.1
Connection and safety notes
S
This manual is an integral part of the equipment. It should be kept close to the equipment for ready reference
whenever needed.
S
For safety reasons, the equipment must not be used for any application other than described in the manual
i.e. only for the intended purpose.
S
Before using the equipment, always check that its limits are suitable for the intended application.
S
Check that the electric power supply is correct for the equipment before connecting it to power.
S
If required, a reverse voltage protection must be installed by the customer, e.g. by means of a coding of the
plug.
S
Specified ambient conditions (e.g. humidity and temperature limits) must be observed and complied with in
order to avoid malfunctioning (see Section 10 - Specifications).
S
Check correct wiring of the connections before switching on power to the equipment.
S
Never operate the equipment without its casing. Before opening the casing the equipment must be switched to
zero potential.
Beware of external voltage at the digital inputs and outputs!
S
Contact the supplier in any malfunction or in case of doubt
S
Note and observe maximum load on relay contacts (see Section 10 - Specifications).
All leads running to and from the VS 300 (except 230 V power supply and signal leads) must be
shielded! This applies in particular to analog inputs (sensor leads) and CAN bus wiring. The leads
must also be installed sufficiently clear of other leads carrying live power. Doing so will avoid faulty
measurements and will protect the equipment from external interference via the analog inputs.
For further details please refer to the manual titled Introduction, General Safety and Connection
Notes.
The error reporting dispatch is not yet functional according to experience during a start-up (no tele
phone line put etc.). It is urgently recommended in such cases to supervise the control over the CAN
bus with a store computer CI 3000 and/or a control terminal AL 300 and to make the error reporting
dispatch possible for example with a GSM modem by mobile telephone net. In stand-alone operation
or as an alternative to monitoring by Store Computer/Operator Terminal, an alarm contact provided
on the controller can be used to transmit alarms via telephone line.
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...