Parameter List and Menu Structure of VS 300
134
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
S
Menu 3-4 Monitoring CL1/CL2
Monitoring
POS: XXXXX
Entry
Default
NT
LT
HP
Dim.
tx-Hi Warn. CL1
XXX °C
High Pressure CL1
alarm is generated if
temperature in CL1 rises above this level
1)
-30 - 55
0
-20
52
°C
tx-Hi Res. CL1
XXX °C
Reset
High Pressure CL1
alarm when
temperature drops below this level
1)
-35 - 48
-5
-2
45
°C
tx-Lo CL1
XXX °C
Low Pressure CL1
alarm is generated if
temperature in CL1 rises above this level;
when activated, compressors of CL1 are
disabled at temperature below this level
-> only with LP control
-50 - 20
-25
-46
10
°C
Del.to-Hi CL1
XXX m
High Pressure CL1
alarm delay
1)
0 - 60
10
10
10
min
Del.to-Lo CL1
XXX m
Low Pressure CL1
alarm delay
0 - 60
10
10
10
min
Min Diff.toCL1
XXX K
Minimum allowed difference to - tc
2)
5..15
---
---
-
K
Starts/h CL1
XX
Max. number of hourly compressor/fan
stage starts in CL1;
only with actuating mode by run time.
4 - 60
10
10
60
1/h
tx-Hi Warn. CL2
XXX °C
High Pressure CL2
alarm is generated if
temperature in CL2 rises above this level;
when activated, compressors in CL1 can
be disabled - only with combination of LP
controller in CL1 and HP controller in
CL2.
-30 - 55
0
-20
52
°C
tx-Hi Res. CL2
XXX °C
Reset
High Pressure CL2
alarm when
temperature drops below this level;
reset compressor disabling CL1
-35 - 48
-5
-2
45
°C
tx-Lo CL2
XXX °C
Low Pressure CL2
alarm is generated if
temperature in CL2 rises above this level;
when activated, compressors of CL2 are
disabled at temperature below this level
-> only with LP control.
-50 - 20
-25
-46
10
°C
Del.to-Hi CL2
XXX m
High Pressure CL2
alarm delay
1)
0 - 60
10
10
10
min
Del.to-Lo CL2
XXX m
Low Pressure CL2
alarm delay
0 - 60
10
10
10
min
Starts/h CL2
XX
Max. number of hourly compressor/fan
stage starts in CL2;
only with actuating mode by run time.
4 - 60
10
10
60
1/h
Stg.tmax HP2
.
XX m
No. of compressors running3) in CL at HP
fault in CL2.
0..
3)
-
-
3)
-
1)
Only shown when control loop is configured as HP controller.
2)
Only show when Control Loop 1 is configured as LP controller and Control Loop 2 as HP controller.
3)
After changing compressor stages in CL1, this value is reset to the new default according to the table be-
low. Only shown when CL1 is configured as LP controller (NT or LT) and RK2 as HP controller:
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...