159
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
11 Specifications of VS 300
11.1 Electrical data
Overvoltage category III / pollution degree 2:
All device connections designed for use with 230 V AC supply voltage
must
be connected to the same phase conductor.
400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II / pollution degree 2
or
Overvoltage category II / pollution degree 1:
Different phase conductors may be used.
400 V AC between neighbouring connection terminals is
permitted!
VS 300
Power supply
230 V AC, 50/60 Hz
Rated power
10 VA
Digital inputs
4 x 230 V AC
Relay outputs
Per expansion stage 4/8/12 x 230 V AC / 2,5 A, changeover relays, floating
Analog inputs 1)
2x pressure transducers 4..20 mA
Inputs not shortcircuit-proof!
Analog outputs 1)
2 x 0..10 V (Leads to analog inputs must be screened.)
External device switch
1 x 230 V AC / 5 A (ohmic load), N.O. single-pole, floating
Fieldbus port
CAN bus, floating
Data ports
TTY (passive)
Archive memory
Compressor run times, starts, activity, messages/alarms
Monitoring function
Watchdog
Real-time clock
Battery-backed, Lithium cell, typically 12 min./yr at 25°C
Temperature range
Transport:
-20 °C ... +80 °C
Operation:
0 °C ... +50 °C
Temperature change
Transport:
max. 20 K/h
Operation:
max. 10 K/h
Relative humidity
(non-condensing)
Transport:
8 % ... 80 %
Operation:
20 % ... 80 %
Atmospheric pressure
Transport:
660 hPa ... 1060 hPa
Operation:
0 °C ... +50 °C
Shock
to DIN EN 60068-2-27
Transport and operation: 30 g
Vibration 10-150 Hz
to DIN EN 60082-2-6
Transport and operation: 2 g
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...