Parameter List and Menu Structure of VS 300
104
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
(1): Minimum of one stage must be defined in
CL:
CL1:
S301
>
0
CL2:
S331
>
0
(2): Only shown when CL configured as HP
controller
NT
LT
HP
S234
S274
Minimum FC speed with
continuous control
0..50
0
0
0
%
(1) and speed controller must be active in respective
CL:
CL1:
S300 > 0
CL2:
S330 > 0
S235
S275
Regulating speed for
analog controller output
with continuous control
-15..15
0
0
0
-
S236
S276
Maximum temperature
with speed control
-35..45
-8
-25
40
°C
S277
No. of compressors run
ning in CLK1 at HP fault
in CL2
0..
1)
-
-
1)
-
(1) and CL1 configured as LP controller
(NT or LT) and CL2 as HD controller.
S238
Minimum allowed diffe
rence between to and tc
5..15 / ---
---
---
-
K
Parameter List S1 and S2:
To change values set access level to
setpoint adjustment enabled
(Parameter A060=1, see section 7.7 Changing the Access Level).
1)
After changing compressor stages in CL1, this value is reset to the new default according to the table below:
No. of compressor stages
Default No. of compressor
stages at HP fault
1 - 2
1
3 - 5
2
6 - 7
3
8 - 10
4
11 - 12
5
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...