Parameter List and Menu Structure of VS 300
121
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
S
Menu 2-1 Analog values
ANALOV.
POS: XXXXX
Act.px
CL1
+/-/=
X.XX bar
Current evaporating/condensing pressure Control Loop 1
Setp.px
CL1
D/N/HR
X.XX bar
Target evaporating/condensing pressure Control Loop 1 for comparison
Act.tx
CL1
+/-/=
X.XX °C
Current evaporating/condensing temperature Control Loop 1
Setp.tx
CL1
D/N/HR
X.XX °C
Target evaporating/condensing temperature Control Loop 1 for comparison
tuIst
RK1
XX °C
Current room/outside temperature Control Loop 1
(only shown when activated)
Feuchte
RK1
Current air humidity Control Loop 1 (only shown when activated)
AnalogOut
RK1
XXX %
Current controller output at analog output for Control Loop 1
(only shown when speed control or combined control is activated)
Act.px
CL2
+/-/=
X.XX bar
Current evaporating/condensing pressure Control Loop 2
Setp.px
CL2
D/N/HR
X.XX bar
Target evaporating/condensing pressure Control Loop 2 for comparison
Act.tx
CL2
+/-/=
X.XX °C
Current evaporating/condensing temperature Control Loop 2
Setp.tx
CL2
D/N/HR
X.XX °C
Target evaporating/condensing temperature Control Loop 2 for comparison
tuIst
RK2
XX °C
Current room/outside temperature Control Loop 1
(only shown when activated)
Feuchte
RK2
Current air humidity Control Loop 2 (only shown when activated)
AnalogOut
CL2
XXX %
Current controller output at analog output for Control Loop 2
(only shown when speed control or combined control is activated)
N
Night operation
px
P
0
or P
c
D Day
operation
tx
t
0
or t
c
HR
Heat recovery mode
+
Temperature high, above neutral zone
-
Temperature low, below neutral zone
=
Temperature within neutral zone
S
Menu 2-2 Compressor/Fan Control Loop 1
CL1-COMP./COND
POS: XXXXX
Stage 1
XXX
Display ON/OFF: Actuating status of digital output, relay/control stage 1
...
Only actual number of compressor/fans in Control Loop 1 is shown
Stage 12
XXX
Display ON/OFF: Actuating status of digital output, relay/control stage 12
1)
1)
Number of relay/control stages CL1 [1..n] + Number of relays CL2 [n+1..m] + Number internal alarm relay
<= Number of relay/control stages VS 300 (max. 4/8/12 depending on expansion stage and configuration),
see section 4.1.1 System Configuration - Allocation of Relay/Control Stages
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...