Alarms and Messages of VS 300
157
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
10.6 System fault reports
RAM error is a fatal error and causes the VS 300 Pack Controller to go into fault status, as correct running of the
program is then no longer likely. The watchdog attempts to reset the controller and force a restart. The controller
will not start if the RAM error is permanent.
Message/alarm No.
LED display VS 300
Display text
AL 300 or CI 3000
System fault report
E000
Internal error
Internal error
E004
EEPROM error
EEPROM parameter memory defective - not responding
E005
EEPROM checks.
Faulty EEPROM content (checksum)
E008
RTC error
Internal clock defective
E009
I/O module error
Internal bus system fault
E010
Battery voltage
Internal battery low
E050
First start
First start with default parameters
E051
Power failure
Restart following power failure
10.7 Process fault reports
Message/alarm No.
LED Display VS 300
Display text
AL 300 or CI 3000
System fault report
E180
Service mode
Service mode active
E181
Fast return
CL1/2
Fast unload active in Control Loop 1 or 2
E182
Load shed
CL1/2
Load shedding active in Control Loop 1 or 2
E203
Sens.type change
Pressure sensor parameter changed
E207
Press.too high HP1
High pressure in Control Loop 1; (LT1, NT1 or HP1)
E208
Press.too high HP2
High pressure in Control Loop 2; (LT2, NT2 or HP2)
E209
Press.too low
CL1
Low pressure in Control Loop 1 (LT1, NT1 oder HP1)
E210
Press.too low
CL2
Low pressure in Control Loop 2 (LT2, NT2 oder HP2)
E211
Meas.err.
CL1
Pressure sensor measuring loop Control Loop 1
E212
Meas.err.
CL2
Pressure sensor measuring loop Control Loop 2
E222
No Load Level CL1
No Load Level in Control loop 1
E223
No Load Level CL2
No Load Level in Control loop 2
E224
No UA 300
No UA 300 found with refrigeration point control
E240
Setpoint changed
Setpoint changed
E241
config. changed
Controller configuration changed: LTLT, LTNT, LTHP, NTNT, NTHP, HPHP, NTLT
E243
Ext. Message E1
Digital alarm input 1 active
E244
Ext. Message E2
Digital alarm input 2 active
E245
Ext. Message E3
Digital alarm input 3 active
E246
Ext. Message E4
Digital alarm input 4 active
Содержание VS 300
Страница 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 158: ...Parameter List and Menu Structure of VS 300 150 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Страница 172: ...Order No s and accessories of VS 300 164 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...