PX200NB
–
Manual
Page 49 / 57
10.
DEVICE PROGRAMMING
Programming of device is possible with “EBS Config 2.0” configuration program
described in chapter 5. To program the device establish connection with a
device.
Depending on connection mode there are two ways for programming.
10.1.
LOCAL PROGRAMING
To program a device locally follow the procedure:
a)
Connect PROG joint (on printed circuit) with COM computer port by way of
service wire, defined in option -> RS-232.
b)
Connect power supply to terminals
+12V
and
GND
. After connection and
detection of programming wire a module shall signal this with LED diodes:
a green one shall flash and red one shall flicker.
c)
Launch software and define device options (description is in chapter 6 of
this Manual). Provide right PIN code for SIM card.
d)
Save settings into memory of device. Saving course is displayed in special
window.
e)
After saving disconnect power supply and disassembly service wire.
f)
Insert SIM card. Connect module wiring pursuant to guidelines from chapter
4. Turn power supply on.
g)
The device is ready to transmit data.
10.1.1.
The first programming of device
As the device does not have defined access parameters in respect of GPRS
network and OSM.Server, programming shall be begun with providing
parameters.
Irrespectively of providing these parameters the first operation shall be
registration of device in OSM.Serverdata base.
Before remote programming user shall check that the device is furnished with
SIM card and is connected to power supply. User shall know serial number of
device and phone number for SIM card.
Follow the procedure:
a)
With the use of OSM.Server console position cursor on proper device in
“Devices” tab.