S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Local Control Troubleshooting Flow Chart
Start
End
No
Yes
Yes
No
No
Yes
No
Yes
Yes
Yes
No
No
Is the
fault LED
lit?
Check Protection LEDs/fault
code and attempt to clear
Check basis for
Stop command
Is Reset mode
set to AUTO?
Possible Transient
fault, set Reset
mode to Manual
Check for
external device
failures
Consult Manual
to diagnose
Fault Code
Fault Code
repeats
Verify Fault
condition does
not exist
Contact Eaton
Support
Fault Condition
not present
Correct fault
condition
Contact Eaton
Support
Unit trips,
fault code
present
Fault
resets
Stop
command
received