S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
45
Motor Protection/Advanced Programming Set Points
The basic operation of the S611 is fully programmable through dedicated Protection and
Operation LEDs (P/O LEDs). More advanced settings are available indirectly (through
parameter codes) by selecting the Operation mode and the Advanced Config parameter.
The following diagram outlines the procedure for editing the advanced set points of the S611.
See table on
Page 41
in
Appendix A—Parameters
for advanced parameters.
Note:
The editing mode can be exited at any time (without saving the parameter value) using
the Mode/Cancel button.
Motor Protection/Advanced Programming Set Points
Step 1:
Press Mode button until Operation mode LED is lit.
Step 2:
Press Up or Down button until Advanced Param P/O LED
is lit.
Display shows the current parameter code.
Step 3:
Press the Edit/Save button. The display now shows
the p
arameter code
but it is now flashing.
Step 5:
Press the Edit/Save button. The display now shows the parameter value
corresponding to the selected parameter code. The value will be flashing as
editing is enabled.
Mode/Cancel
Step 4:
Use the Up/Down buttons to select the desired parameter.
P. 10
P. 10
P. 20
Edit/Save
Edit/Save
Step 6:
Use the Up/Down buttons to select the desired parameter value.
Step 7:
Press the Edit/Save button to store the new parameter value.
140
120
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...