24
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Operation of the user interface is broken into three modes listed across the top of the device.
Pressing the Mode key enables mode navigation.
Interface Mode Keys
The Mode and Protection/Operation (P/O) LEDs are used in conjunction to identify a selected
parameter.
Setup and Starting
Before You Begin
Be Aware of the Following:
1.
The
Permissive
terminal must have 120 Vac applied to ENABLE starts.
2.
To Start: Apply 120 Vac to the
Start
terminal while the
Permissive
terminal is energized.
3.
To initiate a stop, remove the
Permissive
terminal input.
4.
For two-wire control, jumper
Permissive
and
Start
terminal inputs together.
5.
The
Permissive
and
Network
inputs must be energized (120 Vac) to enable starting of the
soft starter from the network.
6.
After an overload trip, the S611 soft starter cannot be restarted until the prescribed
cool-down time has elapsed. Cycling control power does not reset the timer. If 120 Vac
power is removed, the soft starter will remember the remaining time and will resume the
cool-down timing when power is again reapplied.
Mode
Description
Protection
Used to set motor protection thresholds and/or disable protection parameters
Operation
Used to set operational parameters, including auto reset modes
Monitoring
Used to display run-time data parameters
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...