S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
51
S611 Motor Protection Parameters
The S611 implements the following protection features. Each protection feature is individually
configured and enabled by the user. Some of the features are designed to protect the motor
and others are for internal protection of the S611.
Motor Parameters
One or more of the motor protection features need the following motor parameters. The user
must input these values prior to enabling protection.
Motor Parameters Required for Protection
Instantaneous Overcurrent
When the bypass contactors are not engaged, the S611 monitors the maximum rms value
of the three-phase currents. The unit will trip with an instantaneous overcurrent fault if the
maximum value exceeds six times the catalog FLA setting for 1.5 seconds. This internal
protection mechanism is most useful for protecting the S611 from starting a motor too large
for its ratings.
Instantaneous Overcurrent Settings
Motor Stall
The S611 monitors the maximum rms value of the three-phase currents. The unit will trip with
a motor stall fault if the stall fault is enabled and the maximum rms value exceeds the trip
threshold setting when the start time setting expires.
Motor Stall Settings
Parameter
Set Point Range
Step
Default
Notes
Motor rated voltage
130–600
1
480
Settable from the UI
Mode O/P
LED
Operation
Motor rated voltage
Motor FLA
26–414
(depends on unit ID)
FLA <100, 0.1A
FLA >=100, 1A
Depends on unit ID
Settable from the UI
Mode O/P
LED
Operation
Motor FLA
Trip class
Off, 5–30
1
20
Settable from the UI
Mode O/P
LED
Protection
Trip class
Phase sequence
0
= Don’t care
1
= ABC
2
= ACB
N/A
1 = ABC
Settable from UI
Mode O/P
LED
Protection
Phase sequence
Parameter
Set Point Range
Step
Default
Notes
Trip threshold
600% of catalog FLA
N/A
N/A
Not user settable
Trip delay
1.5 seconds
N/A
N/A
Not user settable
Parameter
Set Point Range
Step
Default
Notes
Trip threshold
OFF, 150–300% of
FLA setting
1%
200%
Settable from the UI
Mode O/P
LED
Protection
Stall trip %
Trip delay
N/A
N/A
N/A
Instantaneous rms value at end-of-ramp is used
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...