![Eaton S611 Скачать руководство пользователя страница 58](http://html2.mh-extra.com/html/eaton/s611/s611_user-manual_4102923058.webp)
46
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Fault Display
The S611 indicates most faults with a fault code and by illuminating the corresponding mode
and Protection/Operation (P/O) LEDs. In addition, the dedicated Fault LED will be illuminated
when the device is faulted.
Fault Display
Fault
FC
User Interface
Mode LED
P/O LED
Display
Watchdog firmware
3
None
None
F.03
FRam
5
None
None F.05
User interface com failure
6
None
None
F.06
Flash CRC
7
None
None
F.07
Zero volt cross lost
8
None
None
F.08
Comm lost port A
9
None
None
F.09
Comm lost port B
10
None
None
F.10
Pole over temp
15
None
None
F.15
Bypass dropout
16
None
None
F.16
SCR not firing
17
None
None
F.17
Shorted SCR
18
None
None
F.18
Instantaneous SCR overcurrent
19
None
None
F.19
Motor overload
20
Operation
Motor FLA
F.20
Mains loss
21
Protection
Under voltage (V)
F.21
Under voltage
22
Protection
Under voltage (V)
F22
Over voltage
23
Protection
Over voltage (V)
F.23
Phase reversal
24
Protection
Phase sequence
F.24
Stall
25
Protection
Stall trip %
F.25
SCR overcurrent
27
None
None
F.27
Under load
28
Protection
Under load
F.28
Current imbalance
29
Protection
Current imbalance %
F.29
Phase loss
30
Protection
Phase loss %
F.30
Voltage imbalance
31
Protection
Voltage imbalance %
F.31
Jam
33
Protection
Jam trip %
F.33
Contactor overcurrent
34
None
None
F.34
Missing temp sensor
35
None
None
F.35
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...