S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Start Command Troubleshooting Flowchart
S611 Does Not START
Start Source Attempted
Suggested Corrective Action
Terminal block
Verify that the Ready LED is illuminated prior to the start attempt
Verify that the Fault LED is not illuminated
Verify that the 120V permissive signal is at the proper voltage
Verify that the 120V start signal is at the proper voltage
Verify that there is no voltage to the 120V comms select terminal
If the Start Control parameter is set to Edge, verify that the 120V start signal is transitioned from 0 Vac after a fault trip
Network
Determine if the S611 can be started locally from TB3
Verify that the 120V permissive signal is at the proper voltage
Verify that the 120V comms select terminal is at the proper voltage
Verify that the Fault LED is not illuminated
No
Yes
Yes
No
No
Yes
Yes
Check 120 Vac
power
120 Vac
supply
present
Are any
LEDs lit?
Is the
Fault LED
lit?
Start
Supply 120 Vac
power
Is the
Ready LED
lit?
Check Protection
LED’s and fault
code and attempt
to clear
Check 120V
permissive
Check 120V
start signal
Check 120V
remote CMD
End