Appendix C—Ratings, Cooling and Power Losses
Power Ratings
Note:
Always refer to motor plate FLA and ensure that the motor plate FLA is equal to or
lower than the maximum current value in the tables.
Standard Duty—300% Current for 15 Seconds, 115% Continuous
Standard Duty Plus—350% FLA for 30 Seconds, 115% Continuous
Maximum
Current (Amps)
Horsepower Rating
208V
240V
480V
600V
Catalog Number
52
15
15
40
50
S611A052N3S
65
20
20
50
60
S611A065N3S
77
25
25
60
75
S611A077N3S
99
30
30
75
100
S611B099N3S
125
40
40
100
125
S611B125N3S
156
50
60
125
150
S611C156N3S
180
60
60
150
150
S611C180N3S
242
75
75
200
250
S611D242N3S
302
100
100
250
300
S611E302N3S
361
125
150
300
350
S611E361N3S
414
150
150
350
450
S611F414N3S
Maximum
Current (Amps)
Horsepower Rating
208V
240V
480V
600V
Catalog Number
52
15
15
40
50
S611A052N3S
65
20
20
50
60
S611A065N3S
71
20
25
60
75
S611A077N3S
99
30
30
75
100
S611B099N3S
119
40
40
100
125
S611B125N3S
156
50
60
125
150
S611C156N3S
180
60
60
150
150
S611C180N3S
242
75
75
200
250
S611D242N3S
302
100
100
250
300
S611E302N3S
361
125
150
300
350
S611E361N3S
407
150
150
350
400
S611F414N3S
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...