S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
3
Technical Data and Specifications
Environmental
Environmental Specifications
Physical
Unit Weight and Dimensions
Standard Units
Description
Specification
Temperature range
Operating
–4° to 122°F (–20° to 50°C)
Storage
–40° to 185°F (–40° to 85°C)
Elevation
Up to 6600 ft (2000m) above 6600 ft (2000m), derate 0.5% per 330 ft (100m)
Humidity
Functional to 95% noncondensing
Operating orientation
Vertical, line side up
Pollution degree IEC 60947-1
3
Shock resistance
15g up to 242A units, 5g on 302A to 414A units
Vibration resistance
Non-operating
3g up to 242A units, 2g on 302A to 414A units
Operating
1g for all units
Unit Weight
Lbs (kg)
Product Size—Inches (mm)
Catalog Number
Length
Width
Height
24 (11)
19.45 (494)
11.58 (294)
7.46 (189)
S611A052XXX
24 (11)
19.45 (494)
11.58 (294)
7.46 (189)
S611A065XXX
24 (11)
19.45 (494)
11.58 (294)
7.46 (189)
S611A077XXX
24 (11)
19.45 (494)
11.58 (294)
7.46 (189)
S611B099XXX
24 (11)
19.45 (494)
11.58 (294)
7.46 (189)
S611B125XXX
33 (15)
20.83 (529)
11.58 (294)
8.37 (213)
S611C156XXX
33 (15)
20.83 (529)
11.58 (294)
8.37 (213)
S611C180XXX
38 (15)
20.83 (529)
11.58 (294)
8.37 (213)
S611D242XXX
86 (39)
31.15 (791)
17.56 (446)
9.54 (242)
S611E302XXX
86 (39)
31.15 (791)
17.56 (446)
9.54 (242)
S611E361XXX
102 (46)
31.15 (791)
17.56 (446)
9.54 (242)
S611F414XXX
www.comoso.com
Содержание S611
Страница 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Страница 2: ...www comoso com...
Страница 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Страница 95: ...www comoso com...