10 Parameter list
10.3 Parameter groups for RAMO
166
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
10.3.3 Parameter group 2 (“Extended functions”)
Table 29:
Parameter group 2 (“Extended functions”)
Para
meter
Designation
Description
Unit
Min
Max
DS
P2-24
Start Mode
Defines the behaviour of the drive relating to the enable
digital input and also configures the automatic restart
function.
0: Edge-r : Following power on or reset, the drive will not
start if a start signal (FWD/REV) is still present. To start a
rising edge is necessary.
1: Auto-0 : Following a power on or reset, the drive will
automatically start if digital input 1 is closed.
2, …, 9: Auto-1 to 9 : Following a trip, the drive will make
up to 9 attempts to restart at intervals set in P2-26.
The drive must be powered down to reset the counter.
The number of restart attempts are counted, and if the
drive fails to start on the final attempt, the drive will trip,
and will require the user to manually reset the fault.
–
0
10
0
P2-26
Auto Reset Delay
AutoResetDelay
Determines the time which will elapse between consecu-
tive drive reset attempts when Auto Reset is enabled in P2-
24.
s
0.1
60
0.5
P2-27
Action@Thermistorfault Motor
Device reaction after occuring of “Thermistorfault Motor”.
Possibilities device dependent
0: deactivated
1: activated
–
0
1
1
P2-28
Service Interval Time
Service Interval Time
Defines the number of operating hours, after which the
service indicator is shown on the display.
With P2 -29 = 1 the counter is set to the value defined here.
The remaining time until the next service is indicated with
P0-22.
h
0
60000
0
P2-29
Reset ServiceIndicator
Reset Service Indicator
With P2-29 = 1 the counter for the remaining hours until
the next service is set to the value defined in P2-28.
Reset of P2-29 to 0 is done automatically.
–
0
1
0
P2-30
Parameter Set
Restores factory parameter settings.
–
0
1
0
P2-32
Access Key Level2
Defines the password which is used to get access to
extended parameter set (Level 2).
Access via P1-14.
–
0
65535
101
P2-33
Parameter Lock
Determines whether to lock the parameters
0: OFF. All parameters can be accessed and changed
1: ON. Parameter values can be displayed, but cannot be
changed.
If a remote keypad is connected, parameters cannot be
accessed.
–
0
1
0
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...