3 Installation
3.6 Motor feeder
100
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
3.6.2.1 Motor cable monitoring
Pin 5 and pin 8 of the motor feeder socket are used to monitor the motor
cable’s motor feeder plug and for thermistor protection.
Monitoring is performed depending on the setting in parameter P2-27.
Figure 63: General motor connection with motor feeder plug and motor cable monitoring
3.6.2.2 Motor cable with thermistor connection
Figure 64: General motor connection with thermistor,
motor feeder plug and motor cable monitoring
The cable ends (Pin 5 and Pin 8) on motors with thermistors or thermostats
(thermoclick) must be connected in the terminal box of the motor (T1 - T2).
→
For motor cable monitoring and operation without a thermistor,
the cable ends of PIN 5 and PIN 8 must be bridged in the termi-
nal box of the motor (cable monitoring T1 - T2).
1
7
3
PE
M
3 ~
U
V
W
PE
≦ 20 m
(≦ 65.62 ft)
5
8
1
7
3
PE
T1
T2
M 3 ∼
ϑ
U
V
W
PE
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...