12 Error messages
12.2 RAMO Error list
206
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
12.1.4 Error list
The following table lists the failure codes, the possible causes and indicates
corrective measures.
12.2 RAMO Error list
Table 48:
RAMO Fault messages list
Message
Error no.
Possible cause and remedy
Stop
–
Ready for operation. There is no drive enable signal present. There are no error
messages present.
no-F
(
t
00
Shown for P0-13 if there are no messages in the error register.
I.t-trP
04
Motor overload. The thermal protection mechanism has tripped as a result of
the device being run above the rated motor current set with P1-08 longer than
a specific time.
• Check to make sure that the motor data was entered correctly in P1-08.
• Check the motor's connection configuration (e. g., start/delta).
• Make sure that the motor is not being mechanically blocked and that there
are no additional loads on the motor.
O.Volt
06
Overvoltage in DC link
The DC-Link Voltage value can be viewed using parameter P0-20.
P0-36 contains an error register with the last values before the unit was
switched off (scan time: 256 ms).
• Check to make sure that the supply voltage falls within the range for which
the variable frequency drive is sized.
V.Volt
07
Undervoltage in DC link
Note:
Generally, this message will appear when the supply voltage is switched off
on the device and the DC link voltage dies away.
In this case, there is no fault.
If the message appears during operation:
• Check whether the power supply voltage is too low.
• Check all components/devices in the variable frequency drive's feeder
circuit (circuit-breaker, contactor, choke, etc.) to make sure they are
connected properly and have an adequate contact resistance.
P-dEf
10
The parameters’ default settings have been loaded.
• Press the STOPP button: The drive can then be reconfigured:
SC-ObS
12
Communication fault with an external operating unit or with a PC.
• Check connections.
P-LOss
14
Failure of one phase of the infeed
dAtA-F
17
Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
• Change the parameter values (again) and save them once more.
• If the message appears again, please contact your nearest Eaton sales
branch.
dAtA-E
19
Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
• Change the parameter values (again) and save them once more.
• If the message appears again, please contact your nearest Eaton sales
branch.
F-Ptc
21
Motor PTC thermistor overtemperature
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...