12 Error messages
12.3 RASP Error list
210
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
P-LOss
14
Failure of one phase of the infeed
h O-I
15
Overcurrent at output
• See Error no. 03.
th-f
(
t
16
Malfunctioning heat sink thermistor.
• Please contact your nearest Eaton sales branch.
dAtA-F
17
Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
• Change the parameter values (again) and save them once more.
• If the message appears again, please contact your nearest Eaton sales
branch.
dAtA-E
19
Error in internal memory. The parameters have not been saved and the default
settings have been loaded.
• Change the parameter values (again) and save them once more.
• If the message appears again, please contact your nearest Eaton sales
branch.
F-Ptc
21
Motor PTC thermistor overtemperature
O-hEAt
23
The measured ambient temperature exceeds the specified value.
• Make sure that the required clearance around the device is being main-
tained and that cooling air can flow through the vents on the device unim-
peded.
• Reduce the switching frequency with P2-22.
• If possible: Reduce load.
O-torq
24
Maximum permissible torque exceeded.
• If possible: Reduce the load or increase acceleration time t-acc.
V-torq
25
Underload
If the motor current is 25 % below the rated motor current, this error message
appears.
OVt-F
26
Device output fault
• Please contact your nearest Eaton sales branch.
Sto-F
29
Internal STO circuit fault
• Please contact your nearest Eaton sales branch.
AtF-01
40
Motor identification failed:
The measured stator resistance varies between the phases.
• Make sure that the motor is connected properly and working correctly.
• Check the motor windings to make sure they have the same resistance
values.
AtF-02
41
Motor identification failed:
The measured stator resistance is too large.
• Make sure that the motor is connected properly and working correctly.
• Check to make sure that the device's rated output matches the motor’s
rated output. The difference should not exceed one full output class.
AtF-03
42
Motor identification failed:
The measured motor inductance is too low.
• Make sure that the motor is connected properly and working correctly.
AtF-04
43
Motor identification failed:
The measured motor inductance is too high.
• Make sure that the motor is connected properly and working correctly.
• Check to make sure that the device's rated output matches the motor’s
rated output. The difference should not exceed one full output class.
Message
Error no.
Possible cause and remedy
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...