2.3 Repair and maintenance switch
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
35
2.3 Repair and maintenance switch
The versions RAMO5-…-…RS1 and RASP5-…-…R…S1 are equipped with a
repair and maintenance switch that disconnects the Rapid Link Modules in all
three phases
①
from the mains voltage.
Figure 11: Repair and maintenance switch in position 0 = OFF
→
The motor must be stopped before the repair and maintenance
switch is activated.
DANGER
Before performing maintenance or repair work on RASP5 units,
make sure to wait until the DC link voltage discharging time
(at least five minutes) has passed.
This also applies when handling the motor.
1
4
3
5
2
e
1
2
3
L1
L2
L3
PE
5
4
N
a
e
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...