UPS Installation Plan and Unpacking
3-22
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual
164201725—Rev 10
www.eaton.com/powerquality
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Table 3-4, Table 3-5, Table 3-6, Table 3-7 or Table 3-8 for wiring requirements. If an output lockable
disconnect is required, it is to be supplied by the customer.
Table 3-17 lists the recommended rating for input circuit breakers.
Table 3-18 lists the recommended rating for input circuit breakers with separate rectifier inputs. A separate
breaker is required for each UPM.
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
See Note 2
400 Vac
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
3
(Each UPM)
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
5
3
5
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
4
3
4
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
DC (All
ratings)
Battery
(Positive, Negative, Ground)
See Note 1
NOTE 1 Select conduit taking into consideration the DC input wire sizes listed in Table 3-4, Table 3-5, Table 3-6 and Table 3-7, the DC terminations listed in
Table 3-12, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
NOTE 2 Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for an 825kVA UPS.
NOTE 3 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
Table 3-16. Power Cable Conduit Requirements (Continued)
UPS Model
Voltage
Terminal
Number of Wires in
Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Table 3-17. Recommended Input Circuit Breaker Ratings
UPS Model
Input Rating
Load Rating
400V
480V
Power Xpert 9395-825/650
80% Rated
1600A
1200A
100% Rated
1200A
1000A
Power Xpert 9395-825/750
80% Rated
1600A
1600A
100% Rated
1600A
1200A
Power Xpert 9395-825/825
80% Rated
2000A
1600A
100% Rated
1600A
1200A
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
See Note
80% Rated
2000A
1600A
100% Rated
1600A
1200A
NOTE Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these
breaker sizes are specified for an 825 kVA UPS.