UPS Installation Plan and Unpacking
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
3-17
AC input to the UPS with separate rectifier inputs is wired as if each UPM is rated for 275 kVA (see Table 3-8).
The bypass input, battery input, and output are wired the same as for a separate battery UPS (see Table 3-5 or
Table 3-7).
Terminals E1A through E5A and E9A through E12A are stud type terminals. The intercabinet power wiring
connections for this equipment are rated at 90ºC. See Table 3-10 for external power cable terminations,
Table 3-11 for supplied external wiring terminal hardware.
The torque values listed in Table 3-10 for the M8 studs are the maximum allowable. Tightening further will risk
breaking or twisting the stud.
Figure 4-13 and Figure 4-15 show the location of the power cable terminals inside the UPS.
Table 3-8. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the Three
UPM Power Xpert 9395-825/650, 9395-825/750, and 9395-825/825 and the Two UPM Power Xpert
9395-825/450, 9395-825/500, 9395-825/550 – Separate Battery
Basic Unit Rating
Units
Rating
50/60 Hz
Rating
50/60 Hz
kVA
kW
275
250
275
250
Input and Output Voltage
Volts
400
480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
453 377
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(3)
4/0
(2)
NOTE Callout letter
A
Table 3-9. Neutral Bonding Jumper Wire Size (Four Wire Only - All Ratings)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size Number
AWG or kcmil
(each)
4/0
(1)
Table 3-10. UPS Intercabinet Power Cable Terminations for the Three UPM Power Xpert 9395-825/650, 9395-825/750, and 9395-825/825 and the
Two UPM Power Xpert 9395-825/450, 9395-825/500, 9395-825/550
Terminal Function
Terminal
Function
Bus Landings
Tightening Torque
Nm (lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4)
Phase A
3 – stud mounting
14.2 (10.4)
M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4)
Phase B
3 – stud mounting
14.2 (10.4)
M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4)
Phase C
3 – stud mounting
14.2 (10.4)
M8