UPS Operating Instructions
7-28
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
7.4.2
Enable Energy Saver System Mode from the UPS Command Menu
To enable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE WITH ESS
. The UPM status
indicates
ONLINE
. If the battery is not charging, the power module is off.
7.4.3
Disable Energy Saver System Mode from the UPS Command Menu
To disable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE
. The UPM status indicates
ONLINE
.
7.4.4
Start Energy Saver System High Alert Mode from the UPS Command Menu
To start High Alert mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
NOTE
The Energy Saver System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled,
the Energy Saver System mode commands will not be displayed.
NOTE
The Energy Saver System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled,
the Energy Saver System mode commands will not be displayed.
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled,
the Energy Saver System mode commands will not be displayed.