Introduction
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
1-7
1.2.13 Monitoring and Communication
The UPS system can be further enhanced by adding optional accessories such as a Remote Emergency
Power-off (REPO) control, RMP II, SCM II, RIM II, or X-Slot communication cards. See Chapter 5, “Options”
for additional information.
l
Remote Monitor Panel II (RMP II)
– An optional RMP II contains backlit status indicators and a local horn,
allowing monitoring of the operational status and alarm condition of the UPS from virtually any location
within the facility.
l
Relay Interface Module II (RIM II)
– An optional RIM II uses relay contact closures to indicate the UPS
operating status and alarm condition.
l
Supervisory Contact Module II (SCM II)
– An optional SCM II establishes an interface between the UPS
system equipment and the customer's monitor.
l
X-Slot Cards
– Optional X-Slot cards support several protocols, such as SNMP, HTTP, IBM
®
AS/400
®
, and
Modbus
®
RTU.
l
eNotify Remote Monitoring and Diagnostics Service
– An optional service that provides 24/7 remote
monitoring of 43 alarms, temperature/humidity and battery charge information, daily heartbeat check, and
monthly report. The service also provides customer notification of significant alarms, remote diagnostics,
and dispatch of technicians. A ConnectUPS™-X Web/SNMP Card is required in an X-Slot communication
bay. An optional Environmental Monitoring Probe (EMP) is required for temperature/humidity monitoring
See Chapter 8, “Communication”, for additional information on monitoring and communication features.
1.3
Battery System
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead–acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPMs in distributed bypass and parallel systems must use a separate battery system.
Consult the
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
for
specifics on battery cabinet usage with the PowerXpert 9395.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
1.4
Using This Manual
This manual describes how to install and operate the Power Xpert 9395 UPS (450–550 kVA) cabinet. Read and
understand the procedures described in this manual to ensure trouble-free installation and operation. In
particular, be thoroughly familiar with the REPO procedure (see paragraph 7.3.25 on page 7-26).
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters 1 through 4
and Chapter 7 should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to
the UPS system being installed or operated.
NOTE
The 9395 system can trip a maximum of six battery cabinets total. This applies to
both the 1085 standard and High Rate series batteries. If more than six battery
cabinets in total are needed in a separate UPM battery configuration, DO NOT hook
up the shunt trips.
Содержание Power Xpert 9395 UPS
Страница 2: ......
Страница 27: ...Installation ...
Страница 28: ......
Страница 123: ...Section 2 Operation ...
Страница 124: ......
Страница 249: ......
Страница 250: ... 164201725 10 164201725 10 ...