9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
The RMP II contains a local horn and the backlit status indicators listed in Table 8-1.
Table 8-1. RMP II Status Indicators
SYSTEM NORMAL
The UPS is energized (either with utility power or battery backup) and is supplying
conditioned power to the critical load.
NO REDUNDANCY
This indicator applies only to parallel systems when one cabinet is not functioning.
ON GENERATOR
The UPS input and bypass are being supplied by the power from the generator
instead of from the utility power.
ON BYPASS
The bypass source is supplying the critical load. Usually this means that the UPS is
not energized. The load is not protected in Bypass mode, and a horn sounds after
30 seconds.
UPS ALARM
The UPS system is issuing an alarm. Conditions that affect the current UPS mode
are indicated by the indicators and horn on the UPS.
ON BATTERY
The UPS battery backup is supplying the critical load. The utility power is either
interrupted or out of specification. The SYSTEM NORMAL indicator is also
illuminated.
BYPASS UNAVAILABLE
The UPS system is in Online mode, but a bypass source is not within specification.
A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in Battery mode and the DC
voltage is approaching its low limit. This indicator is accompanied by a horn.