Instructions for installation and use of low temperature kits
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
6.5.2 Vacuum
Because the indoor unit of this unit is equipped with electronic expansion valve, the electronic expansion valve
is closed during shutdown, and there is a one-way valve in the low temperature components (see the system
schematic diagram above). The unit with low temperature components needs to be vacuumed at one of the two
needle valve shown in the figure 6.7 and then system can ensure that the whole pipeline is vacuumed. When a
one-way valve is added to the system pipeline, it is necessary to vacuum the front and back of the one-way valve.
The globe valve of the indoor unit needs to be opened during evacuation.
System schematic diagram of rack air conditioning E04S unit
Indoor side
Needle valve before
expansion valvet
needle valve after
expansion valve
Figure 6.7
System schematic diagram of rack air conditioning E08S unit
Valve front
needle valve
Indoor side
Figure 6.8