Unit installation
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
NOTICE
-
In order to ensure personal safety, a good metal connection must be made between the metal shell
of the unit (the grounding bolt indicated by the label at the bottom of the unit) and the grounding
body after the air conditioner is installed. Please make sure that the user is properly grounded when
installing the machine.
-
The power input of all indoor units is single-phase three-wire (L+N+PE), please pay close attention to
the installation.
-
The cable connecting the indoor and outdoor units is self-equipped by the user.
-
The supply voltage must be in the normal range (187-253V).
-
The original circuit in the unit is not allowed to be changed under any circumstances.
-
Do not connect the wiring of “L” and “N” upside down.
-
All terminals must be installed securely.
-
All the safety protection devices in the unit are set up before leaving the factory, so do not adjust by yourself.
If the unit is damaged by the user’s own adjustment, Eaton Corporation will not be responsible for it.