Instructions for installation and use of low temperature kits
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
6.5.3 Refrigerant charge
Units with cryogenic components.
Rack air conditioner E04S charge refrigeration dose: unit charge without cryogenic comp 2 kg. Rack air
conditioner E08S charge refrigeration dose: unit charge without cryogenic comp 2.5kg.
Note that the charging amount of the unit without cryogenic components is calculated from the installation
instructions of the indoor unit.
6.5.4 Add frozen oil
The addition of refrigerant in the cryogenic components will lead to the dilution of the frozen oil in the system,
which will affect the lubrication and cooling effect of the frozen oil, so it is necessary to add the frozen oil.
Model name
Freezing oil addition
E04SE+EW06E
200 mL
E08SE+EW10E
250 mL
The refueling method and location refer to the installation instructions of the indoor unit.