42
Manual operator (optional kits)
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
Fault
address Alarm name
Alarm reason
Solution
50
Whole machine current
protection U7
The current of the outdoor unit is too high. Check whether the outdoor fan and compressor are blocked. Automatically
reset after troubleshooting
51
Whole machine current
detection fault U6
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
52
DC bus voltage drop U5 Abnormal voltage of power network
Automatically reset after troubleshooting
53
DC input voltage is too
low U4
Abnormal voltage of power network
Automatically reset after troubleshooting
54
DC input voltage is too
high U3
Abnormal voltage of power network
Automatically reset after troubleshooting
55
Feedforward voltage
protection U2
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
56
Charging fault U1
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
57
Foreign EEUROM
failure U0
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
58
PFC protects U9
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
59
PFC current detection
fault U8
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
61
Outdoor exhaust
failure E8
The exhaust temperature probe of the
outdoor unit is cut off.
Check the outdoor exhaust temperature sensor and its wiring. Automatically
reset after troubleshooting
62
Outdoor exhaust short
circuit E4
Short circuit of exhaust temperature probe
of outdoor unit
Check the outdoor exhaust temperature sensor and its wiring. Automatically
reset after troubleshooting
63
Outdoor
communication failure
The communication between the main
controller and the indoor communication
board is abnormal.
Check the wiring between the main controller and the indoor
communication board. Automatically reset after troubleshooting
69
Temperature sensing
short circuit E5 of press
module
The driver circuit of outdoor unit is
abnormal.
Contact the manufacturer for support
70
Outdoor temperature
sensitive short circuit E2
Ambient temperature probe short circuit
of outdoor unit
Check the outdoor ambient temperature sensor and its wiring.
Automatically reset after troubleshooting
71
Internal motherboard
communication fault C3
Abnormal communication between
internal and external computers
Check the wiring of internal and external machines. Automatically reset
after troubleshooting
72
Communication failure
of foreign motherboard
C6
Abnormal communication between
internal and external computers
Check the wiring of internal and external machines. Automatically reset
after troubleshooting
73
Power loss alarm
The power supply is lost and then
restored while the unit is in operation.
It will be released automatically after 10 seconds.
74
Shut off failure of
globe valve
The change of low pressure pressure
during start up of the unit is too small.
Please make sure that the shutoff valve of the indoor and outdoor unit has
been opened. This fault is used to remind the customer to check the shutoff
valve status of the indoor and outdoor unit and reset it manually.
76
Slave 1 is missing
The host cannot communicate with Slave
1 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
77
Slave 2 is missing
The host cannot communicate with Slave
2 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
78
Slave 3 is missing
The host cannot communicate with Slave
3 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
79
Slave 4 is missing
The host cannot communicate with Slave
4 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
80
Slave 5 is missing
The host cannot communicate with Slave
5 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
81
Slave 6 is missing
The host cannot communicate with Slave
6 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
82
Slave 7 is missing
The host cannot communicate with Slave
7 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
83
Slave 8 is missing
The host cannot communicate with Slave
8 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
84
Slave 9 is missing
The host cannot communicate with Slave
9 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
85
Slave 10 is missing
The host cannot communicate with Slave
10 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
86
Slave 11 is missing
The host cannot communicate with Slave
11 in group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting
87
Host missing
The slave cannot communicate with the
host through group control.
Check group control wiring and group control parameter settings.
Automatically reset after troubleshooting