40
Manual operator (optional kits)
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
The parameters of “Unit Running Time” are shown in the following table:
Serial number Name
Display range
Remarks
1
Compressor running time
0~100000
Unit: hours
2
Running time of indoor fan
0~100000
Unit: hours
3
Electric heating running time
0~100000
Unit: hours
4
Running time of external fan
0~100000
Unit: hours
5
Pump running time
0~100000
Unit: hours
6
Running time of compressor is
cleared to zero.
—
The running time will be cleared to zero, and the maintenance of the
compressor will be prompted to reset manually.
7
The running time of indoor fan is
cleared to zero.
—
The running time will be cleared to zero, and the maintenance of the internal
fan will be prompted to reset manually.
8
Running time of electric heating
is cleared to zero.
—
The running time will be cleared to zero, and the electric heating maintenance
prompt will be reset manually.
9
Maintenance time of
external fan
—
The running time will be cleared to zero, and the maintenance of outdoor fan
will be prompted to reset manually.
10
The running time of the pump is
cleared to zero.
—
The running time will be cleared to zero, and the pump maintenance prompt to
reset manually.
5.7 Fault handling
5.7.1 Fault list
Fault
address Alarm name
Alarm reason
Solution
0
Failure of high pressure
pressure probe
Missing or short circuit of high pressure
sensor
Check the high voltage sensor and its wiring, and reset automatically after
troubleshooting.
1
Failure of low pressure
probe
Missing or short circuit of low voltage
pressure sensor
Check the low voltage sensor and its wiring, and reset automatically after
troubleshooting.
2
Suction temperature
probe failure
Missing or short circuit of inspiratory
temperature sensor
Check the suction sensor and its wiring, and reset automatically after
troubleshooting.
3
Failure of supply air
temperature probe
Missing or short circuit of supply air
temperature probe
Check the supply air temperature probe and its wiring, and reset
automatically after troubleshooting.
4
Return air temperature
probe failure
Missing or short circuit of return air
temperature probe
Check the return air temperature and humidity sensor and its wiring, and
reset automatically after troubleshooting.
5
Return air humidity
sensor failure
Missing or short circuit of return air
humidity sensor
Check the return air temperature and humidity sensor and its wiring, and
reset automatically after troubleshooting.
6
Maintenance failure of
indoor fan
The cumulative running time of the part
exceeds the set limit (default 10000 hours)
Reset manually after zero clearing
7
Maintenance failure of
compressor
The cumulative running time of the part
exceeds the set limit (default 10000 hours)
Reset manually after zero clearing
8
Maintenance failure of
outdoor fan
The cumulative running time of the part
exceeds the set limit (default 10000 hours)
Reset manually after zero clearing
9
Electric heating
maintenance fault
The cumulative running time of the part
exceeds the set limit (default 10000 hours)
Reset manually after zero clearing
10
Maintenance failure of
water pump
The cumulative running time of the part
exceeds the set limit (default 10000 hours)
Reset manually after zero clearing
11
High voltage locking
fault
Three high voltage alarms occurred within
1 hour or high voltage alarms were not
reset within 10 minutes.
Check whether the condensing fan is running, check whether the condenser
is dirty and clogged, check whether the degree of undercooling is too high,
and manually reset after troubleshooting.
12
Low voltage locking
fault
There are 3 low voltage alarms within 1
hour or low voltage alarms are not reset
within 10 minutes.
Check whether the refrigerant is leaking, check whether the condenser fan
is running normally, and reset manually after troubleshooting.
13
Low voltage sensor
fault lock
Three low pressure sensor failures
occurred within 1 hour
Check low voltage sensor and its wiring, manually reset after
troubleshooting
14
Exhaust high
temperature lock
There are three exhaust high temperature
alarms within 1 hour or no reset within 10
minutes.
Check whether the condensing fan is running, check whether the condenser
is dirty and clogged, check whether the degree of undercooling is too high,
and manually reset after troubleshooting.
15
Compressor start
failure
After the operation of the unit, the
outdoor compressor did not run.
Check whether the communication between indoor and outdoor machines
is normal, restart the unit after power outage for 1 minute, and reset
automatically after troubleshooting.
16
1#Indoor fan failure
The actual speed of fan 1 does not reach
50% of the control speed.
Check the normal operation of the indoor fan, check whether the wiring of
the indoor fan is correct, and reset automatically after troubleshooting.