Zone Wallstations & Scene Wallstations

www.eaton.com/lightingsystems

Normal Power Connections

The feeding circuit will provide power to the controlled loads 

as well as to the Room Controller’s microprocessor. The 

maximum combined load of the three relays onboard the 

Room Controller should not exceed 20A.
Connect line voltage wiring to the provided leads, matching 

your room configuration to load 1, 2 and 3 according to 

your lighting layout and/or diagram on the Room Controller 

QuicKit.

Connecting Emergency Power Line Voltage

The RC3DE model supports a 3A emergency relay. This is a 

UL 924 listed solution for emergency lighting control.
Under normal power operation, the emergency load will 

track operation to the load tied to the yellow lead (load 1). 

When normal power fails, the emergency relay will close 

and the load will be forced on to full brightness.

Connecting 0-10V Load Wiring

The RC3D and RC3DE models allow for connection of up 

to three 0-10V dimming zones depending on the model. 

Dimming outputs are independent of relay control to 

allow maximum flexibility in application. Switched zones 

and dimmed zones do not need to overlap in the Room 

Controller architecture as relays and dimmers are controlled 

separately.
Route the 0-10V purple and gray wires through one of the 

provided conduit knockouts in the low voltage section. 

0-10V terminal blocks are removable for ease of wiring. 

Connect the 0-10V purple wire to the positive location and 

the gray wire to the negative location on the first dimmer 

terminal block. Repeat for additional dimming zones.

Load 3

Load 2

Load 2

Load 2

Load 1

Load 1

Load 1

Load 1

Load 1

Load 1

Load 1

Load 1

Load 1

Dimmer 1

Dimmer 2

Dimmer 3

Dimmer 3

Dimmer 2

Dimmer 1

Dimmer 1

Dimmer 1

Dimmer 2

Dimmer 2

Dimmer 3

Dimmer 3

Dimming Zone 

1

Dimming Zone 

2

Dimming Zone 

3

1

2

3

4

5

6

Integration Controls

Adjustable Skylights

Low En

dH

igh En

d

Energy Options

Statu

s

Reset

0-10V Gain Adjustmen

t

Dimmer 3

Dimmer 2

Dimmer 1

+

-

-

+

+

-

0-10V Dimming

Blue - EM Line In Blue - EM Loads Out

CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation

.

Black - Line In White/Black - 120V 

N

White/Orange - 277V 

N

Blue - Load In Ye

llow - Load 1 Ou

t

Red - Load 2 Out Purple - Load 3 Out

0-10V Dimming Outputs

-

+

Dimmer 3

Dimmer 2

Dimmer 1

-

+

+

-

Energy Options DIP Switch

Demand Response Occupancy

Not Used

1 2

3

4

Default 10%

20%

30%
40%

Occ

Vac (default)

Time

Clock

Alert

Mode

Demand

Response

A/V

Mode

+

-

Integration Controls

+

-

+

-

+

Green

Black

Red

White

Adjustable Skylight

s

Sensors

Receptacle

BMS/Out

Switchpack

QuickConnect Cable

s

Sensors

Slider

Station

Wallstations

-

+

-

-

+

+

-

Dimmer 3 Dimmer 2 Dimmer 1

0-10V Dimming

(RC3DE Model Shown)

 0-10V Gray (-)

 0-10V Violet (+)

Ntee:

N

For daylight dimming applications, 

dimmer 1 should be the zone closest 

to the window. Dimmer 3 is the zone 

furthest from the window.

Zone Wallstations & Scene Wallstations

Half Lights

Full Lights

Under 

cabinet

All OFF

Lower

Raise

Specifications

Voltage

24 VDC supplied from Room 

Controller

Electrical

Class 2, LPS

Connections

Two onboard QuickConnect ports

Installation

Standard decorator opening

Operating Environment

32° F to 104° F (0° to 40° C) 

For indoor use only.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...

Отзывы: