8

Daylight Sensor / IR Receiver

www.eaton.com/lightingsystems

If you have a larger room that requires two occupancy 

sensors, the second sensor’s input/output device may 

attach directly to the first sensor’s input/output device or 

may be routed to the second sensor Click & Go port on the 

Room Controller.

OR

1

2

3

4

5

6

Integration Controls

Adjustable Skylights

Low End

High End

Energy Options

Status

Reset

0-10V Gain Adjustment

Dimmer 3

Dimmer 2

Dimmer 1

+

-

-

+

+

-

0-10V Dimming

0-10V Dimming Outputs

-

+

Dimmer 3

Dimmer 2

Dimmer 1

-

+

+

-

Blue - EM Line In Blue - EM Loads Out

CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.

Black - Line In White/Black - 120V N White/Orange - 277V N

Blue - Load In Yellow - Load 1 Out

Red - Load 2 Out Purple - Load 3 Out

Energy Options DIP Switch

Demand Response Occupancy

Not Used

1 2

3

4

Default 10%

20%

30%

40%

Occ

Vac (default)

Time

Clock

Alert

Mode

Demand

Response

A/V

Mode

+

-

Integration Controls

+

-

+

-

+

-

Green

Black

Red

White

Adjustable Skylights

Sensors

Receptacle

BMS/Out

Switchpack

QuickConnect Cables

Sensors

Slider

Station

Wallstations

1

2

3

4

5

6

Integration Controls

Adjustable Skylights

Low End

High End

Energy Options

Status

Reset

0-10V Gain Adjustment

Dimmer 3

Dimmer 2

Dimmer 1

+

-

-

+

+

-

0-10V Dimming

0-10V Dimming Outputs

-

+

Dimmer 3

Dimmer 2

Dimmer 1

-

+

+

-

Blue - EM Line In Blue - EM Loads Out

CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.

Black - Line In White/Black - 120V N White/Orange - 277V N

Blue - Load In Yellow - Load 1 Out

Red - Load 2 Out Purple - Load 3 Out

Energy Options DIP Switch

Demand Response Occupancy

Not Used

1 2

3

4

Default 10%

20%

30%

40%

Occ

Vac (default)

Time

Clock

Alert

Mode

Demand

Response

A/V

Mode

+

-

Integration Controls

+

-

+

-

+

-

Green

Black

Red

White

Adjustable Skylights

Sensors

Receptacle

BMS/Out

Switchpack

QuickConnect Cables

Sensors

Slider

Station

Wallstations

QuickConnect Cable

(Class 2)

Model: OCC-RJ45

Occupancy Sensor Coupler

Brown

Black

Red

Blue

Model: OCC-RJ45

Occupancy Sensor Coupler

Brown

Black

Red

Blue

OCC-RJ45

(Input/Output Device)

OCC-RJ45

(Input/Output Device)

QuickConnect Cable

(Class 2)

OCC-RJ45

(Input/Output Device)

Model: OCC-RJ45

Occupancy Sensor Coupler

Brown

Black

Red

Blue

OCC-RJ45

(Input/Output Device)

Model: OCC-RJ45

Occupancy Sensor Coupler

Brown

Black

Red

Blue

Daylight Sensor / IR Receiver

The Room Controller connects to one daylight sensor 

for multi-zone dimming control in the RC3D and RC3DE 

models.

Specifications

Voltage

24 VDC supplied from Room 

Controller

Electrical

Class 2, LPS

Light Sensor Range
 Low:

3-300 lux

 High:

30-3000 lux

  Direct Sun:

300-30000 lux

Connections

Sensor has a Click & Go ready 

connector to a provided  

GGRC-COUPLER.

Operating Environment

32° F to 104° F (0° to 40° C) 

For indoor use only.

Mounting

The daylight sensor can be mounted to a ceiling tile or fixture 

using the threaded post and locking washer in materials up to a 

0.75” thick. The accessory mounting bracket (DSCM-MT) allows 

the daylight sensor to be mounted to a hard wall.

 

Ensure the daylight sensor is not obstructed and is not looking 

directly at electric lighting

 

For skylights that contain motor controls, ensure the daylight 

sensor is mounted below the daylight blocking mechanism

 

Remember to adjust the sensor head to point the arrow and 

lens in the correct position

 

Ensure the daylight sensor is not looking out the window or 

skylight

Functions

The daylight sensor adjusts the light level in the space based 

on natural light. The daylight sensor is an open loop sensor that 

controls all three zones in the Room Controller. Out-of-the-box 

the Room Controller and daylight sensor provide three daylight 

dimming levels for primary, secondary and top lighting. The out-

of-the-box daylight levels target approximately 45 fc at the work 

surface across the space depending on room size and fixture 

spacing. 
The daylight sensor also acts as an IR receiver for the HHPR-RC 

personal remote and is required if the space needs an IR personal 

remote.
Room Controller wallstations allow the user to lower the light level 

below the daylight level setting. The Room Controller wallstations 

will never allow the light level to be raised above the daylight level 

setting.

Skylight Location

Narrow Location

60°

60°

60°

Mount the daylight sensor 

one to two times the 

window height from the 

window wall. Position the 

sensor so its lens and 

arrow is pointed toward the 

window.

Area Viewed By
Daylight Sensor

Area Viewed by
Daylight Sensor

For skylights mount the  
daylight sensor on the south  
wall of the skylight well so 
that the lens is aimed at the 
north wall, with the arrow and 
lens pointed up.

For narrower spaces 

mount the daylight 

sensor near the window 

with the sensor lens and 

arrow facing away from 

the window and pointing 

into the space.

Area Viewed By
Daylight Sensor

Ceiling Location

Sensor Cable to Coupler

(GGRC-COUPLER)

Threaded

Mounting Post

Adjustable Daylight

Sensor Dome

Daylight Sensor

Viewing Lens

Ceiling

Locking Washer

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...