Room Controller Troubleshooting

www.eaton.com/lightingsystems

Lights turn ON  

but remain at a 

dimmed level  

(lighting does not 

respond to dimming 

raise controls)

Slider Station

 

If a slider station is installed, other raise lower controls will be disabled. Verify that the slider operates 

as intended.

0-10V  

Output

 

Disconnect 0-10V terminal blocks from the Room Controller. Lighting should go full bright:

 

If lighting does not go full bright, check all wiring and ballasts/drivers for miswires and shorts on the 

0-10V wiring until the problem is found.

 

Verify with a meter that at least 10 VDC is present between the purple and gray disconnected leads. 

The Room Controller is a sink device (requires the ballast/driver provide the dimming voltage).

 

If lighting does go full bright when disconnected from the Room Controller, check for polarity reversal 

on the 0-10V leads.

 

Reconnect 0-10V wiring to the Room Controller. Press the reset button on the Room Controller to verify 

that lighting turns ON and goes full bright for 3 seconds:

 

If it does go to full bright before resuming the dimmed level refer to the Demand Response and 

Daylighting possible causes.

 

If lighting does not go full bright during the 3 second reset period, check that the maximum trim level 

potentiometer is not set too low for the space.

Demand 

Response

 

Demand Response Mode may have caused light levels to automatically reduce.  Check contact from 

demand response system. Verify that the demand response Energy Options DIP Switches are set for the 

appropriate lighting level.

Daylighting

 

Daylight levels may not be correct for your space. Press the reset button on the controller to verify loads 

turn ON to Full ON for 3 seconds. If loads go Full ON then resume dimmed level:

 

Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily. If it is, the sensor 

is seeing more daylight than its range will allow.  Set a new range using the HHPRG-RC remote and 

the Advanced Daylight Level Adjustment procedures in the installation instructions.

 

If the Daylight Sensor’s green LED is not on, use the HHPRG-RC remote to adjust daylight levels per 

the Advanced Daylight Level Adjustment procedures in the installation instructions.

 

Check the High End trim pot to ensure it is not set all the way counter-clockwise.

Lights turn ON but 

remain at a full 

bright level  

(lighting does not 

respond to dimming 

lower controls)

Slider Station

 

If a slider station is installed, other raise lower controls will be disabled.  Verify that the slider operates 

as intended.

0-10V  

Output

 

Disconnect 0-10V terminal blocks from the Room Controller. Lighting should remain full bright:

 

Temporarily remove the 0-10V wiring for a zone and then connect the purple and gray wires together. 

Verify that the load goes full dim. If the load does not go full dim, check all wiring and ballasts/drivers 

for miswires and shorts until the problem is found.

 

Verify with a meter that at least 10 VDC is present between the purple and gray disconnected leads. 

The Room Controller is a sink device (requires the ballast/driver provide the dimming voltage).

 

If lighting does go full dim when disconnected from the Room Controller, check for polarity reversal on 

the 0-10V leads.

 

Reconnect 0-10V wiring to the Room Controller and continue with the additional troubleshooting steps 

listed below.

Alert Mode

 

If Alert Mode has been activated, lighting will be ON and full bright until the alert is cleared. Disconnect 

contact into the Alert Mode terminal to verify normal  operation resumes. Troubleshoot the connected 

system to determine the cause of the alert signal.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...

Отзывы: