10
Receptacle Control Switchpack
www.eaton.com/lightingsystems
Receptacle Control Switchpack
The Room Controller connects to five Receptacle Control Switchpacks for control of 20A receptacle circuits. Receptacles
will be turned on when the occupancy sensor senses motion (even when in Vacancy Mode) or when any switch button is
pressed to turn lighting loads ON. Controlled receptacles will switch OFF when the occupancy sensor no longer senses
motion or, in applications where there is no occupancy sensor, when commanded into After-Hours Mode from an external
contact. The receptacle output will not blink warn in After-Hours Mode.
Mounting and Connection
The Receptacle Control Switchpack mounts to a standard four inch square junction box. All line voltage connections are made
via flying leads. Connect the Receptacle Rated Switchpack to the Room Controller using one of the provided QuickConnect
cables. If connecting more than one Receptacle Control Switchpack to the Room Controller, use the GGRC-SPLITTER
accessory.
5
QuickConnect Cable
(Class 2)
Connect a QuickConnect cable between
the Receptacle Rated Switchpack and
the Receptacle/BMS Click & Go port
on the Room Controller.
SPRC-R-20-120
(Receptacle Rated Switchpack)
Click & Go Port
Line Voltage Wiring
to Receptacle(s)
120VAC Hot
Neutral
Black
White/Black
Blue
Blue
Line In
J BOX
Receptacle
1
2
3
4
5
6
Integration Controls
Adjustable Skylights
Low End
High End
Energy Options
Status
Reset
0-10V Gain Adjustment
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In White/Black - 120V N White/Orange - 277V N
Blue - Load In Yellow - Load 1 Out
Red - Load 2 Out Purple - Load 3 Out
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
-
Green
Black
Red
White
Adjustable Skylights
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cables
Sensors
Slider
Station
Wallstations
CAUTION
The Receptacle/BMS out port supports the use of a
Receptacle Switchpack or BMS Output. Do not tie both
items into the port at the same time. Presence of the
Receptacle Switchpack will cause 24 VDC to be present
on the BMS output, which may cause damage to the
connected system.