Advanced Integration Connections

www.eaton.com/lightingsystems

Input

Function

Position

Operation

Time Clock 

Mode

 

Time Clock Mode will not operate if occupancy sensors 

are attached to the Room Controller.

 

For use with Room Controllers not connected to 

occupancy sensors. 

 

Switches the controller between After-Hours Mode and 

Normal Mode.

 

Contact Type Required: Normally Open, SPST 

Maintained.

 

Time clock input will vary if there is no occupancy 

sensor connected to the Room Controller

Open

Occ Sensor Connected & Occupied:
DIP#3&#4 ON lighting = SCENE 6, Rec=ON
DIP#3ON, #4OFF lighting = ALL ON, Dim 50%, Rec=ON
DIP#3&#4 OFF lighting = Manual ON, Rec=ON
Occ Sensor Connected & UnOccupied:
Lighting = OFF
Receptacle = OFF (30seconds after lighting)
No Occ Sensor Connected:
Lighting = Blink warn OFF (5min)
Manual ON button press has a 1hr timer
Receptacle = OFF (30 seconds after lighting)

Closed

Occ Sensor Connected & Occupied:
DIP#3&#4 ON lighting = SCENE 6, Rec=ON
DIP#3ON, #4OFF lighting = ALL ON, Dim 50%, Rec=ON
DIP#3&#4 OFF lighting = Manual ON, Rec=ON
Occ Sensor Connected & UnOccupied:
Lighting = Scene 5
Receptacle = ON
No Occ Sensor Connected:
Lighting = Scene 5
Receptacle = ON

Pulse

Occ Sensor Connected & Occupied:
Lighting= No Change
Receptacle = ON
Occ Sensor Connected & UnOccupied:
Lighting = OFF
Receptactle = OFF (30 seconds after lighting)
No Occ Sensor Connected:
Lighting = Blink warn OFF (5min)
Receptact = OFF (30 seconds after lighting)

Alert Mode

 

Overrides system functions to allow for fire alarm, 

emergency or other systems needing to call lighting to 

a full ON condition.

 

Contact Type Required: Normally Open,  SPST 

Maintained.

Closed

Onboard relays close. Dimmers go to full. Solatubes open. 

Receptacle Switchpack turns OFF. Wallstation, occupancy and 

daylight controls are disabled.

Open

System is returned to normal function leaving lighting in 

current state. If no occupancy sensor closure is detected, 

lighting will blink warn and turn OFF 5 minutes later.

Demand  

Response 

Mode

 

Dimmers reduce current level and maximum output by 

10%, 20%, 30% or 40% based on DIP Switch setting.

 

Contact Type Required: Normally Open, SPST 

Maintained.

Closed

Dimmers reduce by selected percentage over a 2 minute 

period. Controller continues to operate lighting within the 

reduced range.

Open

Lighting range will revert to full scale.

A/V Mode

 

Allows a 3rd party device or system to activate and 

de-activate the A/V scene.

 

Contact Type Required: Normally Open, SPST 

Momentary.

Momentary 

Closure

Toggles between A/V Mode and Normal Mode. In A/V Mode, 

relays will stay in their previous configuration. Dimmers will 

be reduced to maintain light levels at 20%

 by default or other 

light level if reprogrammed using the Room Controller Personal 

Remote (HHPR-RC).

*Connected alternate voltage and receptacle switchpacks will not blink warn with onboard relay loads. They will remain ON 

during the blink warn process and will turn OFF with other lighting once the warning periods expire.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...